Protection Relays & Protection Couplers

Protection relays detect faults on lines, transformers and busbars and trip the right circuit breaker within milliseconds. On a transmission line, the relay at each end must also know what the relay at the far end sees — that is the job of the protection coupler (tele-protection equipment), which carries trip and permissive commands between substations over PLCC, fibre optic multiplexers or direct fibre.

Protection relays

What each relay protects

ANSI 21

Distance protection

Measures impedance to the fault and trips in stepped zones (Zone 1 / 2 / 3). The main protection for 132 KV and 220 KV lines.

ANSI 87L

Line current differential

Compares currents at both ends of the line over a communication channel. Needs a fast, low-latency fibre path.

ANSI 87T

Transformer differential

Detects internal faults in power transformers by comparing currents on the HV and LV sides.

ANSI 50/51 · 50N/51N

Overcurrent & earth fault

Instantaneous and time-delayed protection for feeders, and back-up protection for lines and transformers.

ANSI 87B

Busbar protection

Isolates only the faulted bus section, keeping the rest of the substation in service.

ANSI 50BF

Breaker failure

When a breaker fails to open, trips the surrounding breakers — locally, and at the remote end through an intertrip.

ANSI 27/59 · 81

Voltage & frequency

Under / over voltage and frequency protection for generating plants at the grid interface.

Protection couplers

Carrying the trip command to the far end

A protection coupler sits between the protection relay and the communication channel. It converts relay contact commands into coded signals, delivers them to the far end within a guaranteed time, and rejects channel noise so that no false trip is issued. Tele-protection performance — transmission time, security and dependability — is specified in IEC 60834-1.

Communication channels

  • Analog PLCC

    Commands travel as coded carrier signals on the HV line itself — through the PLCC terminal, line matching unit (LMU), coupling capacitor and wave traps.

  • Digital — PDH / SDH MUX

    Commands ride a 64 kbps or E1 (G.703) channel of the fibre optic multiplexer, or an IEEE C37.94 optical interface, over OPGW.

  • Direct fibre

    Relay-to-relay over dedicated fibres in the OPGW — the usual path for line current differential (87L).

Command types

  • Permissive

    Lets the remote relay trip faster when it also sees the fault.

  • Blocking

    Stops the remote relay from tripping for a fault outside the protected line.

  • Direct / intertrip

    Trips the remote breaker unconditionally — for breaker failure and transformer or reactor protection.

Tele-protection over PLCC

SUBSTATION ASUBSTATION B132 / 220 KV line carries the PLCC signalSendTripBus AWave trapWave trapBus BCVT + LMUCVT + LMUPLCC terminalPLCC terminalDistance relay21Distance relay21Protection couplerProtection coupler
HV power lineSerial / hard-wired (RS485, RS232, I/O)PLCC (power line carrier)Swipe to see full diagram →

Tele-protection over fibre (OPGW) and MUX

SUBSTATION ASUBSTATION BOPGW on the transmission lineDedicated fibres — line differential (87L)Line relay21 / 87LPDH / SDH MUXC37.94 · G.703 · E1FODPOPGW approachFODPOPGW approachPDH / SDH MUXC37.94 · G.703 · E1Line relay21 / 87L
Optical fibre / OPGWSwipe to see full diagram →
Schemes

Tele-protection schemes

PUTT

Permissive Underreach Transfer Trip

Zone 1 is set to reach short of the far end. When it operates, it trips the local breaker and sends a permissive signal; the remote relay trips instantly if its own overreaching Zone 2 has also picked up.

POTT

Permissive Overreach Transfer Trip

Each end sends a permissive signal when its overreaching zone sees a forward fault. A breaker trips when its own overreaching zone and the received permissive signal coincide — fast clearance for faults anywhere on the line.

DCB

Directional Comparison Blocking

A reverse-looking element sends a blocking signal for faults behind the relay. A breaker trips on a forward fault only if no block is received within a short coordination time.

DTT

Direct Transfer Trip (Intertrip)

The received command trips the remote breaker directly, without a local fault check. Used for breaker failure, transformer and reactor protection — it demands the highest channel security.

87L

Line Current Differential

Current samples from both ends are exchanged continuously over fibre and compared; any difference means an internal fault. Fully selective, and independent of zone settings.

What we deliver

Protection and tele-protection at STEL

Sub Station Automation (SAS) solutions

Complete automation solutions including fiber optic communication systems for tele-protection in 132 KV level substations in solar and wind power plants.

Total analog PLCC communication solutions

Utility approved brands of PLCC panels along with accessories like wave traps, LMUs and FSK modems — total supply and installation for IEC-101 serial data and voice applications.

OPGW / ADSS cable & PDH MUX

Utility approved brands of FOTE PDH MUX panels for IEC-101 serial communication, IEC-104 IP communication, tele-protection and VOIP phone systems, along with OF cable supply and laying.

Protection relays, RTUs and PLCs

Siemens RTUs, protection relays and PLCs, and Schneider MiCOM series RTUs, supplied through our business associates.

Need tele-protection on a new line?

PLCC, PDH MUX over OPGW or direct fibre — we supply, install and test the complete channel with the protection relays.